simpl.
物业检查指挥中心 17 项

EV Charger Installation Inspection

此检查清单为英文版。

A code-compliance and condition inspection of a Level 2 electric vehicle supply equipment (EVSE) installation, covering circuit sizing, GFCI/disconnect provisions, mounting, and functional charging.

NEC Article 625SAE J1772UL 2594

免费 PDF 或 Word · 输入邮箱即可下载。

Installation Details

  • Property address and charger location *
  • Charger level and connection *
  • EVSE manufacturer and rated amperage *
  • Installation is indoor (garage) or outdoor *

Circuit and Overcurrent Protection

  • EVSE is on a dedicated branch circuit *
  • Breaker and conductor are sized to at least 125% of continuous load *
  • Panel has adequate capacity or a load-management device is installed *
  • GFCI/GFPE protection is provided per code and outlet type *

Mounting and Wiring

  • Unit is mounted securely at the correct height with proper cord management *
  • Outdoor equipment and receptacle are weather-rated (NEMA 3R or better)
  • Wiring method, conduit, and connections are secure with correct terminations *
  • Disconnecting means is provided where required (over 60A or over 150V to ground)

Function and Documentation

  • Charger powers on and completes a handshake/charge session with a vehicle or tester *
  • No error indicators, overheating, or connector damage observed *
  • Installation permit and inspection sign-off are available
  • Photo of the unit, connections, and breaker
  • Deficiencies and recommendations

下载完整的EV Charger Installation Inspection检查清单