Fire Sprinkler (NFPA 13) & Fire Alarm (NFPA 72) Acceptance Checklist
Esta lista de verificación está en inglés.
An acceptance and commissioning checklist for verifying automatic sprinkler and fire alarm systems are installed and tested per NFPA 13 and NFPA 72 before occupancy.
NFPA 13NFPA 72NFPA 25IBC 2021 Ch. 9
PDF o Word gratuito · introduzca su correo electrónico para descargar.
Design & Approval Documentation
- Are approved sprinkler and fire alarm shop drawings on site? *
- Are hydraulic calculations and water supply data available for the sprinkler system? *
- Does the installed occupancy hazard classification match the design basis? *
- Is the AHJ notified in advance of the acceptance test? *
Sprinkler System Installation
- Are sprinkler head types, temperature ratings, and spacing correct for the hazard? *
- Are clearances to obstructions and deflector-to-ceiling distances compliant? *
- Are hangers, bracing, and seismic restraints installed where required? *
- Is the fire department connection (FDC) accessible and labeled? *
- Are spare sprinklers and a wrench provided in the spare cabinet? *
Sprinkler Testing
- Has the underground and aboveground piping passed a 200 psi hydrostatic test for 2 hours? *
- Have underground mains been flushed at the required flow rate? *
- Has the main drain (flow) test been performed and readings recorded? *
- Has the inspector's test connection actuated the waterflow alarm within 90 seconds? *
Fire Alarm System
- Are all initiating and notification devices installed per approved plans? *
- Have 100% of installed devices been functionally tested? *
- Is audible/visible notification (candela, dBA) verified in occupied areas? *
- Has off-site monitoring/supervising station signal transmission been confirmed? *
- Is secondary (battery) power capacity verified for the required standby period? *
Commissioning & Records
- Is the contractor's material and test certificate completed and signed? *
- Is a record (as-built) drawing set provided to the owner? *
- Are operation and maintenance manuals delivered? *
- Acceptance test date
Descargue la lista de verificación Fire Sprinkler (NFPA 13) & Fire Alarm (NFPA 72) Acceptance Checklist completa
Obténgala gratis como PDF limpio e imprimible o como documento de Word editable.