Healthcare Facility Compliance 19 items
NFPA 101 Life Safety Code Survey for Healthcare Occupancies
Life Safety Code building and fire-protection survey checklist for hospitals and nursing facilities based on the CMS-adopted 2012 edition of NFPA 101.
NFPA 101 (2012 ed.)CMS 42 CFR 482.41 / 483.90NFPA 99
Free PDF · enter your email to download.
Means of Egress
- Are exit corridors, aisles, and stairways kept clear and unobstructed to a required clear width? *
- Are exit signs illuminated and readily visible from any direction of egress travel? *
- Is emergency egress lighting provided and tested (30-second monthly, 90-minute annual)? *
- Do doors in a means of egress swing in the direction of egress travel where required and latch properly? *
Fire & Smoke Barriers / Compartmentation
- Are smoke barriers subdividing floors into compartments intact with self-closing cross-corridor doors? *
- Are fire-rated doors self-closing, positive-latching, and free of hold-open devices not tied to the alarm? *
- Are penetrations of fire/smoke barriers sealed with an approved firestop system? *
- Are hazardous areas (soiled linen, trash collection >64 gal, storage >50 sq ft) properly separated? *
Automatic Sprinkler & Fire Alarm Systems
- Is the automatic sprinkler system inspected, tested, and maintained per NFPA 25? *
- Is a minimum 18-inch clearance maintained below sprinkler heads to stored materials? *
- Is the fire alarm system tested and maintained per NFPA 72 with documented results? *
- Date of most recent annual fire alarm system inspection? *
Portable Fire Extinguishers & Cooking
- Are portable fire extinguishers appropriately located, mounted, and inspected monthly / serviced annually? *
- Is commercial cooking equipment protected by a UL 300 hood suppression system serviced semi-annually? *
Utilities, Medical Gas & Building Services
- Is the essential electrical (emergency) generator tested monthly under load and maintained per NFPA 110? *
- Are medical gas systems (oxygen storage, zone valves, alarms) maintained per NFPA 99? *
- Are HVAC/heating equipment and grease-producing operations maintained to prevent fire hazards? *
Fire Response & Drills
- Are fire drills conducted quarterly per shift and documented? *
- Is a written fire safety plan (RACE/PASS) available and are staff trained on their roles? *
Download the full NFPA 101 Life Safety Code Survey for Healthcare Occupancies checklist
Get it as a clean, printable PDF — free.
